2 
 Features 
 • Detects voltage circuit failures 
 • Can be used to switch to an 
 alternative supply if the main 
 supply fails 
 • Compact design 
 • Mechanically stable 
 Application 
 The MVAP 22 is essentially a fuse 
 failure relay with changeover output 
 contacts enabling its use for either 
 voltage selection or fuse failure 
 protection. A typical application as 
 a voltage selection relay is the 
 automatic connection of metering 
 equipment to an alternative supply if 
 the normal or preferred supply fails. 
 As a fuse failure relay it will monitor 
 the output of a voltage transformer 
 and give an alarm or disconnect 
 protection circuits for VT fuse failure. 
 The relay monitors the three phase 
 voltage supply and operates if the 
 supply is interrupted or becomes 
 unbalanced due to failure of the 
 voltage transformers primary or 
 secondary fuses. 
 Voltage failure detection on 
 generator VTs 
 The Type MVAP 22 relay can be 
 applied to provide an equivalent 
 function to the voltage balance relay 
 by using one MVAP 22 per voltage 
 transformer and connecting the 
 output contacts of the two MVAP 22 
 relays as shown in Figure 3. 
 The relay combination can be used 
 to block relays or other devices that 
 will operate incorrectly when a 
 voltage transformer primary and/ or 
 secondary fuse( s) blow or to give 
 an alarm for the faulty voltage 
 transformer. 
 Each relay is supplied from its own 
 voltage transformer and will detect 
 blown fuses in either the primary or 
 secondary windings of the voltage 
 transformer or if the voltage supply 
 becomes interrupted. 
 In the event of a generator short 
 circuit causing the voltage supplied 
 to the relays to become appreciably 
 unbalanced the relays will operate,  
 but the trip circuit via the generator 
 protective relays ( ie., devices 21,  
 32 and 40) will be maintained 
 through the normally closed contacts 
 on the two changeover contacts 
 A– 1 and B– 1, and an alarm will be 
 prevented via the normally closed 
 contacts A– 3 and B– 2. 
 Failure of any voltage transformer 
 supply will cause operation of the 
 appropriate MVAP 22 relay and 
 block tripping of the associated 
 generator relays which may be 
 adversely affected by the loss of 
 voltage supply via contacts A– 1 or 
 B– 1 and give an alarm via A– 2 or 
 B– 3. 
 Description 
 Two attracted armature units are 
 employed as shown in Figure 3. 
 Unit A is fed from a resistance/  
 capacitance network which under 
 healthy conditions with negligible 
 harmonics has zero output. 
 An operating voltage appears 
 across the coils of unit A when the 
 secondary voltages become 
 unbalanced due to loss of any one 
 primary or secondary phase. Unit B 
 has six changeover contacts for 
 voltage selection and is normally 
 energised via the normally closed 
 contact on unit A from two phases 
 of the supply. Unit B drops off on 
 operation of unit A, on complete 
 loss of supply, or on loss of two 
 primary or secondary phases. 
 If three limb core type star 
 connected voltage transformers are 
 used, the relay will not operate 
 correctly if the star points of the 
 primary windings are connected to 
 neutral or earth. |